A circuit breaker is an automatically-operated electrical switch which is designed to protect an electrical circuit from damage caused by overload or short circuit. Unlike a fuse which operates once and then has to be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation. Circuit breakers are made in varying sizes, from small devices which protect an individual household appliance up to large switchgear designed to protect high voltage circuits feeding an entire city.
Some circuit breakers are implemented using a solenoid (electromagnet) whose pulling force increases as the current increases. The circuit breaker's contacts are held closed by a latch and, as the current in the solenoid increases, the solenoid's pull releases the latch which then allows the contacts to open by spring action. Another method of sensing current is with a bimetallic strip, which heats and bends with increased current, and is similarly arranged to release the latch. Some circuit breakers incorporate both techniques, with the electromagnet responding to short, large surges in current (short circuits) and the bimetallic strip responding to less extreme but longer-term overcurrent conditions.
Circuit breakers for larger currents are usually arranged with pilot devices to sense a fault current and to operate the trip opening mechanism.
Under short-circuit conditions, a current many times greater than normal can flow (see maximum prospective short circuit current). When electrical contacts open to interrupt a large current, there is a tendency for an arc to form between the opened contacts, which would allow the flow of current to continue. Therefore, circuit breakers must incorporate various features to divide and extinquish the arc. In air-insulated and miniature breakers an arc chute structure consisting (often) of metal plates or ceramic ridges cools the arc, and blowout coils deflect the arc into the arc chute. Larger circuit breakers such as those used in electrical power distribution may use vacuum, an inert gas such as sulfur hexafluoride or have contacts immersed in oil to suppress the arc.
The maximum short-circuit current that a breaker can interrupt is determined by testing. Application of a breaker in a circuit with a prospective short-circuit current higher than the breaker's rating may result in failure of the breaker to safely interrupt a fault.
Small circuit breakers are either installed directly in equipment, or are arranged in a breaker panel. Power circuit breakers are built into switchgear cabinets. High-voltage breakers may be free-standing outdoor equipment or a component of a gas-insulated switchgear line-up.
When supplying a branch circuit with more than one live conductor, each live conductor must be protected by a breaker pole. To ensure that all live conductors are interrupted when any pole trips, a "common trip" breaker must be used. These may either contain two or three tripping mechanisms within one case, or for small breakers, may externally tie the poles together via their operating handles. Two pole common trip breakers are common on 120/240 volt systems where 240 volt loads (including major appliances or further distribution boards) span the two out-of-phase live wires. Three pole common trip breakers are typically used to supply three phase power to large motors or further distribution boards.
High-voltage breakers are broadly classified by the medium used to extinguish the arc.
High voltage breakers are routinely available up to 765 kV AC.
Live tank circuit breakers are where the enclosure that contains the breaking mechanism is at line potential, that is, "Live". Dead tank circuit breaker enclosures are at earth potential.
High-voltage circuit-breakers have greatly changed since they were first introduced about 40 years ago, several interrupting principles have been developed that contributed successively to a large reduction of the operating energy.
Current interruption in a high-voltage circuit-breaker is obtained by separating two contacts in a medium, such as sulfur hexafluoride (SF6), having excellent dielectrical and arc quenching properties. After contacts separation, current is carried through an arc and is interrupted when this arc is cooled by a gas blast of sufficient intensity.
Gas blast applied on the arc must be able to cool it rapidly so that gas temperature between the contacts is reduced from 20,000 K to less than 2000 K in a few hundred microseconds, so that it is able to withstand the Transient Recovery Voltage that is applied across the contacts after current interruption. Sulfur hexafluoride is generally used in present high-voltage circuit-breakers (of rated voltage higher than 52 kV).
In the 1980s and 1990s, the pressure build up necessary to blast the arc has been generated mostly by gas heating using arc energy, it has been then possible to use low energy spring operating mechanism to drive high-voltage circuit-breakers, up to 800 kV.
The achievement around 1983 of the first single-break 245 kV and the corresponding 420kV to 550 kV and 800kV, with respectively 2, 3, and 4 chambers per pole, lead to the dominance of SF6 circuit breakers in the complete range of high voltages.
Several characteristics of SF6 circuit-breakers can explain their success:
The reduction in the number of interrupting chambers per pole has led to a considerable simplification of circuit-breakers as the number of parts was decreased as well as the number of seals. As a direct consequence, the reliability of circuit-breakers was improved, as verified later on by CIGRE surveys.
The last ten years have seen the development of the self-blast technique of interruption for SF6 interrupting chambers. This technique has proved to be very efficient and has been widely applied for high voltage circuit breakers up to 550 kV. It has allowed the development of new ranges of circuit breakers operated by low energy spring-operated mechanisms. These developments have been facilitated by the progress made in digital simulations that were widely used to optimize the geometry of the interrupting chamber and the linkage between the poles and the mechanism. New types of SF6 breaking chambers, which implement innovative interrupting principles, have been developed over the course of the past 15 years, with the objective of reducing the operating energy of the circuit-breaker. One aim of this evolution was to further increase the reliability by reducing the dynamic forces in the pole and its mechanism.
The reduction of operating energy was mainly achieved by the lowering energy used for gas compression and by making increased use of arc energy to produce the pressure necessary to quench the arc and obtain current interruption. Low current interruption, up to about 30% of rated short-circuit current, is obtained by a puffer blast.
Further development in the thermal blast technique was made by introducing a valve between the expansion volume and the compression volume. When interrupting low currents the valve opens under the effect of the overpressure generated in the compression volume. The blow-out of the arc is made as in a puffer circuit breaker thanks to the compression of the gas obtained by the piston action. In the case of high currents interruption, the arc energy produces a high overpressure in the expansion volume, which leads to the closure of the valve and thus isolating the expansion volume from the compression volume. The overpressure necessary for breaking is obtained by the optimal use of the thermal effect and of the nozzle clogging effect produced whenever the cross-section of the arc significantly reduces the exhaust of gas in the nozzle. In order to avoid excessive energy consumption by gas compression, a valve is fitted on the piston in order to limit the overpressure in the compression to a value necessary for the interruption of low short circuit currents.
This technique, known as “self blast” has now been used extensively for more than 10 years for the development of many types of interrupting chambers. The better knowledge of arc interruption obtained by digital simulations and validation of performances by breaking tests, contribute to a higher reliability of these self blast circuit-breakers. In addition the reduction in operating energy, allowed by the self blast technique, leads to a higher mechanical endurance.
An important decrease in operating energy can also be obtained by reducing the kinetic energy consumed during the tripping operation. One of the possible means consists in displacing the two arcing contacts in opposite directions so that, for each of them, the speed is half what would be necessary in a conventional layout with a single mobile contact.
The thermal and self blast principles has enabled the use of low energy spring mechanisms for the operation of high voltage circuit breakers, they progressively replaced the puffer technique since the 1980s, first of all in 72.5 kV, then from 145 kV to 800 kV.
The double motion technique allows to divide by two the tripping speed of the moving part. In principle the kinetic energy could then be divided by four if the total moving mass was not increased. However, as the total moving mass is increased the practical reduction in kinetic energy is closer to 60%. The total tripping energy further includes the compression energy, which is almost the same for both techniques. Thus, the reduction of the total tripping energy is lower, namely approximately 30%, although the exact value depends on the application considered and in particular on the operating mechanism. Depending on the specific case, the double motion technique or single motion one is more economical. Of course, other considerations have to be taken into account, for example rationalization of the circuit-breaker range.
In this interruption principle arc energy is used, on the one hand to generate the blast by thermal expansion and, on the other hand, to accelerate the moving part of the circuit breaker when interrupting high currents. The overpressure produced by the arc energy downstream of the interruption zone is applied on an auxiliary piston linked with the moving part. The resulting force accelerates the moving part, thus increasing the energy available for tripping.
With this interrupting principle it is possible, during high-current interruptions, to increase by about 30% the tripping energy delivered by the operating mechanism and to maintain the opening speed independently of the current. It is obviously better suited to circuit-breakers with high breaking currents such as Generator circuit-breakers.
Generator circuit-breakers are connected between a generator and the step-up voltage transformer. They are generally used at the outlet of high power generators (100 MV·A to 1800 MV·A) in order to protect them in a sure, quick and economic manner. Such circuit breakers must be able to allow the passage of high permanent currents under continuous service (6,300 A to 40,000 A), and have a high breaking capacity (63 kA to 275 kA). They belong to the medium voltage range, but the TRV withstand capability required by ANSI/IEEE Standard C37.013 is such that the interrupting principles developed for high-voltage range must be used . A particular embodiment of the thermal blast technique has been developed and applied to generator circuit-breakers:
The self blast technique, as described above, is also widely used for SF6 Generator circuit breakers operated by low energy spring-operated mechanism,as illustrated by the figure below showing a 17.5 kV 63 kA circuit breaker.
The operating energy has been reduced by 5 to 7 times during this period of 27 years. This illustrates well the great progress made in this field of interrupting techniques for high-voltage circuit-breakers.
In the near future, present interrupting technologies can be applied to circuit-breakers with the higher rated breaking currents (63 kA to 80 kA) required in some networks with increasing power generation.
Self blast or thermal blast circuit breakers are nowadays accepted world wide and they are in service for high voltage applications since about 15 years, starting with the voltage level of 72.5 kV. Today this technique is also available for the voltage levels 420/550/800 kV.
The following types are described in separate articles.
Electricity distribution | Switches
Leitungsschutzschalter | Interruptor magnetotérmico | Disjoncteur | Interruttore magnetotermico | מפסק אוטומטי מגנטי תרמי | 遮断器 | 서킷브레이커
This article is licensed under the GNU Free Documentation License.
It uses material from the
"Circuit breaker".
Home Page • arts • business • computers • games • health • hospitals • home • kids & teens • news • physicians • recreation• reference • regional • science • shopping • society • sports • world