HVAC (pronounced either "H-V-A-C" or, occasionally, "H-VAK") is an initialism/acronym that stands for "heating, ventilating and air-conditioning". This is sometimes referred to as climate control.
These three functions are closely interrelated, as they control the temperature and humidity of the air within a building in addition to providing for smoke control, maintaining pressure relationships between spaces, and providing fresh air for occupants. In modern building designs, the design, installation and control systems of these functions are integrated into a single "HVAC" system.
In certain regions (e.g., UK), the term "Building Services" is also used and HVAC Engineers are called Building Services Engineers. See CIBSE.
The term air handler can mean a whole unit including the blower, heating and cooling elements, filter racks or chamber and dampers, but not including the ductwork through the building.
Heating systems may be classified as central or local.
Central heating is often used in cold climates to heat private houses and public buildings. Such a system contains a central boiler, furnace or heat pump to heat water, steam, or air; piping or ductwork to distribute the heated fluid, and radiators to transfer this heat to the air. The term radiator in this context is misleading, since most heat transfer from the heat exchanger is by convection, not radiation. The radiators may be mounted on walls, or buried in the floor to give under-floor heating. When so mounted it is often referred to as "radiant heating".
All but the simplest systems have a pump to circulate the water and ensure an equal supply of heat to all the radiators. The heated water is often fed through another heat exchanger inside a storage cylinder to provide hot running water.
Forced air systems send air through ductwork. During warm weather, the same ductwork can be reused for air conditioning. The forced air can be filtered or put through air cleaners. Contrary to fiction, most ducts cannot fit a human being as this would require a greater duct-structural integrity and create a potential security liability.
The heating elements (radiators or vents) should be located in the coldest part of the room, and typically next to the windows to minimize condensation. Popular retail devices that direct vents away from windows -- to prevent "wasted" heat -- defeat this design parameter. Drafts contribute more to the subjective feeling of coldness than actual room temperature. Thus rather than improving the heating of a room/building, it is often more important to control the air leaks.
The invention of central heating is often credited to the ancient Romans, who installed a system of air ducts in walls and floors of public baths and private villas. The ducts were fed with hot air from a central fire.
Water heating is more efficient for heating buildings and was the standard many years ago but since forced air systems can double for air conditioning, they are more popular nowadays. The most efficient central heating method is geothermal heating.
Energy efficiency can be improved even more in central heating systems by introducing zoned heating. This allows a more granular application of heat similar to non-central heating systems. Zones are controlled by multiple thermostats which, in water heating systems, control zone valves or, in forced air systems, control zone dampers inside the vents which selectively block the flow of air.
Ventilation is the changing of air in any space in order to remove moisture, odors, smoke, heat, and airborne bacteria. Ventilation includes both the exchange of air to the outside as well as circulation of air within the building. It is one of the most important factors for maintaining healthy indoor air quality in a building. Methods for ventilating a building may be divided into natural and forced types.
Natural ventilation is the ventilation of a building with outside air without the use of a fan or other mechanical system. It can be achieved with operable windows when the spaces to ventilate are small and the architecture permits. In more complex systems, warm air in the building can be allowed to rise and flow out upper openings to the outside (stack effect) thus forcing fresh cool air to be drawn into the building naturally though openings in the lower areas. These systems use very little energy but care must be taken to ensure the occupants' comfort. The natural ventilation flow rate can be calculated with this equation:Natural Ventilation Lecture (scroll to section 3.3)
Forced ventilation may be used to control humidity or odours. Kitchens and bathrooms typically have mechanical ventilation to control both. Factors in the design of such systems include the flow rate (which is a function of the fan speed and exhaust vent size) and noise level. If the ducting for the fans traverse unheated space (e.g. an attic), the ducting should be insulated as well to prevent condensation on the ducting. Direct drive fans are available for many applications (these save the owner the costs of maintaining/replacing drive belts).
Heat recovery ventilation systems employ heat exchangers to bring the fresh air temperature to room temperature.
Ceiling fans and table/floor fans are very effective in circulating the air in the room. Paradoxically, because heat rises ceiling fans may be used to keep a room warmer.
Displacement-ventilation systems introduce air at low velocities which causes minimal induction and mixing. The displacement outlets are usually located at or near the floor. The system utilizes buoyancy forces (generated by heat sources such as people, lighting, computers, electrical equipment, etc.) in a room to move contaminants and heat from the occupied zone. By so doing, the air quality in the occupied zone is generally superior to that achieved with mixing ventilation.
Displacement ventilation presents an opportunity to improve both the thermal comfort and indoor air quality (IAQ) of the occupied space. Displacement ventilation takes advantage of the difference in air density between an upper contaminated zone and a lower clean zone. Cool air is supplied at low velocity into the lower zone. Convection from heat sources creates vertical air motion into the upper zone where high level return outlets extract the air. In most cases these convection heat sources are also the contamination sources, i.e. people or equipment, thereby carrying the contaminants up to the upper zone, away from the occupants.
Outlets are typically located at or near the floor level, and air is supplied directly into the occupied zone. This supply air is spread over the entire floor and then rises as it is heated by the heat sources in the occupied zone. Returns are typically located at or close to the ceiling and exhaust the warm contaminated room air.
Since the conditioned air is supplied directly into the occupied space, supply air temperatures must be higher than mixing systems (usually above 63 °F) to avoid cool temperatures at the floor. By introducing the air at elevated supply air temperatures and low outlet velocity a high level of thermal comfort can be provided with displacement ventilation.
Proper ventilation in the attic:
Be aware that increased ventilation decreases the effectiveness of any insulation that is a poor barrier to air infiltration, such as fiberglass batts. The increased ventilation will create low pressure areas, so that the house will push conditioned air through the insulation faster than it normally would.
With insufficient ventilation:
You will need more ventilation than usual if:
Most houses treat the attic and basement as unconditioned space. You can think of unconditioned space as outdoor space, minus the rain and snow. The unconditioned space surrounding the living area shouldn’t be wide open, but it shouldn't be sealed shut either. A good compromise is to have two foundation vents in the basement and two different types of vents in the attic. Vents should always exist in pairs (but not necessarily two of the same type) to allow for cross-ventilation. In an attic, one member of the pair should be low on the roof, and the other member should be higher up, so that outside air is pulled through one and out the other. Natural attic ventilation through these vents is usually sufficient. Powered vents in the attic may interfere with proper furnace and fireplace venting.
Some ways to ventilate an attic naturally:
Modern homes often incorporate all three types of attic vents, providing continuous cross-ventilation via multiple air pathways.
Make sure gable vents have screens to keep out insects and animals, and keep the screens clean to maintain proper ventilation.
Never close or block off the vents to a damp basement or crawlspace, except in extreme cold to prevent pipes from freezing. Closing the vents to a damp basement or crawlspace will cause mold, rot, and structural defects. Sometimes, a basement or crawlspace will look bone dry, but is transpiring moisture through the dirt floor at a rapid rate. To see if this is the case, lay down some clear plastic on the dirt floor for a few days and observe how much water collects on its underside.
If your basement or crawlspace is dry and has been dry for several years, you can:
Advantages of insulating a dry basement and crawlspace and making them part of the conditioned space of the house:
To provide security and fresh air cooling, some building have using two sets of overhead doors at hot boiler and equipment rooms. The second set of doors are custom made grills with bird screens (similar to the security grills used by some stores at indoor shopping malls). Some of the custom grills have solid slats in the lowest 3' section, to reduce the amount of trash that might blow into the rooms. During hot weather, the grills secure the opening while the solid doors are fully open. During cool and cold weather, the solid doors can be partially or fully closed.
Building Services is a construction body that covers the essential services that allow buildings to operate. It includes the electrotechnical, heating, ventilating, air conditioning, refrigeration and plumbing industries.
Building Services is part of a sector that has over 51,000 businesses and employs over 500,00 people. This sector has an annual turnover of £19.3 billion which represents 2%-3% of the GDP.
Within the construction sector, it is the job of the building services engineer to design, install and maintain the essential services such as gas, electricity, water, heating and lighting, as well as many others. These all help to make buildings comfortable and healthy places to live and work in.
To train as a building services engineer, the academic requirement is GCSEs (A-C) / Standard Grades (1-3) in Maths and Science, which are important in measurements, planning and theory. Employers will often want a degree in a branch of engineering, such as building environment engineering, electrical engineering or mechanical engineering.
An air-conditioning system provides heating, cooling, ventilation and humidity control for a building. It is often installed in modern offices and public buildings, but is difficult to retrofit (install in a building that was not designed to receive it) because of the bulky air ducts required. A duct system must be carefully maintained to prevent the growth of pathogenic bacteria in the ducts. The alternative to large ducts to carry the needed air to heat or cool an area is the use of remote coils or split systems. These systems are gaining popularity in commercial buildings although are most often seen in residential application. The remote coil is connected to a remote condenser unit using piping instead of ducts. The units usually have a fan to move air across the coil, although recent innovation have seen static units installed in some large office spaces.
A dehumidifier is an air-conditioning-like device that controls the humidity of a room or building. They are deployed in basements, which because of their lower temperature (and propensity for damp floor and walls) have a higher relative humidity. In food retailing establishments large open chiller cabinets are highly effective at dehumidifing the internal air. (Conversely a humidifier increases the humidity of a building.)
Air-conditioned buildings often have sealed windows, because open windows would disrupt the attempts of the control system to maintain constant air quality.
For example, a 5000 Btu/h air-conditioning unit, with a SEER of 10, operating for a total of 1000 hours during an annual cooling season (i.e., 8 hours per day for 125 days) would provide an annual total cooling output of:
which, for a SEER of 10, would be an annual electrical energy usage of:
and that is equivalent to an average power usage during the cooling season of: